SPECIFICATIONS
- Measurement line type: 
   + Single-phase 2-wire, single-phase 3-wire
   + Three-phase 3-wire, threephase 4-wire
   + Voltage 4 channels, Current 4 channels
   + Isolated between each channel
- Measurement items: 
   + Voltage, Current, Voltage/current waveform peak
   + Active power, Phase angle, Frequency, Current integration 
   + Reactive power, Apparent power, Power factor
   + Power integration, Efficiency, Loss, Voltage/current ripple factor
   + Noise measurement,RMS spectrum of voltage/current Harmonic measurement
   + RMS value, Content factor, Phase angle
   + Total distortion, Disequilibrium factor
   + Additional functions: Torque, Rotation, Frequency, Slip, or Motor output
- Harmonic measurement:
   + Input: 4 channels, Synchronization frequency range: 0.5 Hz to 5 kHz
   + Number of harmonic orders: Max. 100th order
- Noise measurement:
   + Number of channels: 1ch (select one channel from CH1 to CH4)
   + Maximum analysis frequency: 100k/50k/20k/10k/5k/2kHz
- Measurement range:
   + 15~1500V, 7 ranges
   + 400mA to 500A (20A/50A/200A/500A)
   + Power range: 6.0000 W to 2.2500 MW 
   + Frequency: 0.5 Hz to 5 kHz
- Basic accuracy(45Hz to 66Hz):
   + Voltage: ±0.05 % rdg. ±0.05 % f.s
   + Current: ±0.05 % rdg. ±0.05 % f.s
   + Active power: ±0.05 % rdg. ±0.05 % f.s
- Synchronization frequency range: 0.5 Hz to 5 kHz
- Frequency band: DC, 0.5 Hz to 150 kHz
- Data update rate: 50ms
- Display refresh rate: 200ms
- Data save interval: OFF, 50~500ms,1~30s, 1~60min, 15settings
- External interfaces:
   + LAN, USB (communication/ memory)
   + RS-232C, CF card, Synchronization control
- Power supply: 100~240V AC, 50/60Hz, 140VA max.
- Product Net Weight: 4.8 kg
- Product Size: 340*170*157mm
- Supplied accessories:
    + Instruction Manual for Model 3390-10 ×1
   + Measurement Guide ×1
   + Power cord ×1, USB cable ×1, D-sub connector ×1
   + Color label ×2
- The warranty period: 12 month